LSZH sheath, LTS3
Low smoke halogen free thermoplastic. Red or white as standard. The aluminium tape screen is bonded to the inside of the sheath, so stripping the sheath takes the screen with it.
Product range
A low smoke zero halogen, screened fire performance cable with silicone E12 insulated solid conductors and an aluminium tape bonded to the outer sheath. LPCB approved under certificate 1812d to BS 6387:2013 Category CWZ and EN 50200:2015 Class PH30.
Ordering codes
Two core with CPC, solid conductor, supplied on robust plastic reels. Other lengths, core counts and sheath colours are available to order.
| Sheath | Conductor | 100m reel | 500m reel |
|---|---|---|---|
| Red | 1.5mm² | SH-FRC215-R100 | SH-FRC215-R500 |
| Red | 2.5mm² | SH-FRC225-R100 | SH-FRC225-R500 |
| White | 1.5mm² | SH-FRC215-W100 | SH-FRC215-W500 |
| White | 2.5mm² | SH-FRC225-W100 | SH-FRC225-W500 |
The LPCB approval covers 1.0mm², 1.5mm² and 2.5mm² solid conductors in 2, 3 and 4 core constructions. Sizes outside the stock list above are supplied to order — ask us for a lead time.
Construction
Low smoke halogen free thermoplastic. Red or white as standard. The aluminium tape screen is bonded to the inside of the sheath, so stripping the sheath takes the screen with it.
A full aluminium tape screen with a tinned copper drain wire gives a high level of data protection on signalling and audio circuits.
Fire resistant low smoke zero halogen silicone insulation over bare solid copper, with mica tape in the lay-up rather than on the conductors.
Technical data
| Property | 1.5mm² | 2.5mm² |
|---|---|---|
| Conductor diameter (solid) | 1.38 ± 0.02 mm | 1.78 ± 0.02 mm |
| Approximate overall diameter | 7.40 mm | 8.00 mm |
| Approximate weight | 9.5 kg / 100 m | 14.1 kg / 100 m |
| Conductor resistance | 12.1 Ω / km | 7.41 Ω / km |
| Voltage drop (DC or 1φ AC) | 29 mV / A / m | 18 mV / A / m |
| Current rating — clipped direct | 19.5 A | 27 A |
| Current rating — enclosed | 16.5 A | 23 A |
| Capacitance, core to core | 70 pF / m avg. | 80 pF / m avg. |
| Capacitance, core to screen | 130 pF / m avg. | 145 pF / m avg. |
| Working voltage | 500 V core to core • 300 V core to CPC (Uo/U 300/500 V) |
|---|---|
| Conductors | Bare solid copper |
| Core insulation | Fire resistant low smoke zero halogen silicone, E12 |
| Screening | Aluminium tape, bonded to the outer sheath |
| Drain wire | Tinned copper |
| Outer sheath | Low smoke halogen free thermoplastic, LTS3 |
| Sheath colours | Red, white — other colours to order |
| Insulation resistance | Greater than 10 MΩ |
| Minimum bend radius | 6 × overall diameter |
| Operating temperature | −40 °C to +90 °C |
| Installation temperature | 0 °C to +70 °C |
| Warranty | 10 years from date of manufacture, marked on the cable |
Current ratings are quoted at 30 °C ambient. Refer to BS 7671 for derating factors. Technical data is reproduced from the manufacturer's catalogue CAT.NO.SH/FRC/10/24; confirm against the current datasheet before specification.
Approvals
LPCB certificate 1812d, issue 01, was issued by BRE Global Ltd on 29 August 2024 to Shield Fire, Safety and Security Ltd for the SH-FRC cable types. It is held in force by regular surveillance and a maintained ISO 9001 certificate, and can be checked on RedBookLive.
| Standard | Requirement | Result |
|---|---|---|
| BS 6387:2013 | Fire, water and mechanical shock | Categories C, W, Z |
| EN 50200:2015 | 830 °C fire with mechanical shock | Class PH30 |
| EN 50200:2015 Annex E | 30 min — 15 min fire and water spray, shock every 5 min | Pass |
| EN 60754-1:2014 | Halogen acid gas evolved | Less than 0.5% |
| EN 61034-2:2005+A2:2020 | Smoke density, light transmittance | Greater than 60% |
| EN 60332-1-2:2004 | Vertical flame propagation, single cable | Complies |
Certification is held by the manufacturer, Shield Fire, Safety and Security Ltd. DAT Cable Supplies Ltd is an independent distributor. The certificate and catalogue are issued with every order and are available on request — email [email protected].